Skip to content
Check The Charge Without Connecting Gauges - Part 2 episode artwork

Jun 14, 2017 54 min

Check The Charge Without Connecting Gauges - Part 2

from HVAC School - For Techs, By Techs

In this second part of the podcast, Jim Bergmann wraps up the steps to check a system charge without connecting a gauge manifold. You can check the charge without gauges if you use the following process (and know your DTD, CTOA, etc.): Take the dry-bulb temperature. (Let's say it's 70°F in this example.) Subtract the DTD (35°F). Add target superheat (10°F). Check the suction line. It should be 45°F in this example. If your probe senses a temperature that is NOT within 5°F of the temperature you calculated, check the filter, evaporator coil, etc., for dirt. If the system is not dirty, check the charge with gauges. For a more extensive look at the process in writing, check out THIS article. If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

Episode details come from the podcast's RSS feed.

Embed this episode

Ready to play

Check The Charge Without Connecting Gauges - Part 2

0:00 54:17

No transcript yet.

Requests help us decide what to transcribe next.

Frequently asked questions

How long is this episode of HVAC School - For Techs, By Techs?

This episode is 54 minutes long.

When was this HVAC School - For Techs, By Techs episode published?

This episode was published on June 14, 2017.

Can I download this HVAC School - For Techs, By Techs episode?

Yes. Use the download control on the episode player to save the publisher-provided media file.