EPISODE · Jul 19, 2026 · 3 MIN
EPA 608 Prep 10, Leak Repair Requirements and the 50-Pound Threshold
from Trades Exam Prep
This podcast is made by Ran Chen, who holds an EA license, Insurance and Securities licenses (Series 6, 63, 65), and the CFP® designation. He is passionate about opening access to high-quality exam preparation resources and helping learners prepare more effectively for professional certification exams. In this episode you will learn: - The 50-pound charge threshold that triggers mandatory EPA 608 leak repair requirements for ozone-depleting substances. - The specific annual leak rate thresholds for comfort cooling (10%), commercial refrigeration (20%), and industrial process refrigeration (30%). - That owners have 30 days to complete repairs once a leak rate threshold is exceeded, including verification tests. - The crucial difference between being exempt from mandatory repair (under 50 lbs) and the universal illegality of venting refrigerant. - About the major rule change effective January 1, 2026, which lowers the threshold to 15 pounds for HFC refrigerants under the AIM Act. For more free exam prep tools, practice questions, and AI-powered explanations, visit https://open-exam-prep.com/ or YouTube Channel: https://www.youtube.com/@Open-exam-prep