EPISODE · Aug 7, 2026 · 2 MIN
EPA 608 Prep 29, Operating in a Vacuum — How Low-Pressure Systems Pull in Air
from Trades Exam Prep
This podcast is made by Ran Chen, who holds an EA license, Insurance and Securities licenses (Series 6, 63, 65), and the CFP® designation. He is passionate about opening access to high-quality exam preparation resources and helping learners prepare more effectively for professional certification exams. In this episode you will learn: - Why leaks in low-pressure chillers draw air and moisture INTO the system instead of venting refrigerant out. - That the primary indicator of a leak in a low-pressure system is high condenser (head) pressure. - The function of a purge unit is to continuously remove non-condensables that enter through leaks. - How to perform a leak test by pressurizing the system with dry nitrogen, never exceeding 10 psig. - The crucial exam trap assuming low-pressure systems leak outward like high-pressure systems. For more free exam prep tools, practice questions, and AI-powered explanations, visit https://open-exam-prep.com/ or YouTube Channel: https://www.youtube.com/@Open-exam-prep
Embed this episode
NOW PLAYING
EPA 608 Prep 29, Operating in a Vacuum — How Low-Pressure Systems Pull in Air
No transcript for this episode yet
Similar Episodes