Skip to content
Short #89 - Liquid Line Temperature episode artwork

Mar 24, 2020 13 min

Short #89 - Liquid Line Temperature

from HVAC School - For Techs, By Techs

In this short podcast episode, Bryan explains how to use liquid line temperature as a quick diagnostic indicator on split A/C systems. Liquid line temperature is one of the first things to check when you approach a system. Checking that temperature is also a great way to get into non-invasive testing. The temperature should be between 4 and 15 degrees warmer than the outdoor temperature (unless it is wet). If the liquid line is cooler than the environment, then there could be a restriction. If there is a restriction, you could have a clogged liquid line drier or a partially closed service valve. When you have a larger condenser coil in relation to your capacity, your liquid line will be closer to the ambient temperature; the refrigerant must be at a higher temperature than the outdoor air to give off heat. You should also not see a pressure drop across the liquid line. An important value is the condensing temperature over ambient (CTOA). On a normally operating piece of equipment, the condensing temperature will be 15-30 degrees above the outdoor temperature. The CTOA is a design feature that sets the differential between the saturation temperature and the ambient temperature. So, before the refrigerant subcools, it will be 15-30 degrees above the outdoor ambient temperature. Subcooling goes below the CTOA. If we have a 30-degree CTOA and subtract 10 degrees of subcooling, then our liquid line will be about 20 degrees above the ambient temperature. If you add up all the numbers and find that the liquid line is warm, then you likely have an airflow restriction (dirty condenser, etc.). You shouldn't see a temperature differential across the liquid line; if you see one, then you likely have a restriction in the liquid line or lines that are too long. Learn more about Refrigeration Technologies HERE. If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

Episode details come from the podcast's RSS feed.

Embed this episode

Ready to play

Short #89 - Liquid Line Temperature

0:00 13:34

No transcript yet.

Requests help us decide what to transcribe next.

Frequently asked questions

How long is this episode of HVAC School - For Techs, By Techs?

This episode is 13 minutes long.

When was this HVAC School - For Techs, By Techs episode published?

This episode was published on March 24, 2020.

Can I download this HVAC School - For Techs, By Techs episode?

Yes. Use the download control on the episode player to save the publisher-provided media file.