Occupancy Hazard Classification & Design Density | MN Journeyman Exam Prep
from MN Journeyman Sprinkler Fitter Exam Prep Hosted by CaseyJames669
Occupancy hazard classification and what it does to your design, for the Minnesota journeyman sprinkler fitter exam. NFPA 13 (2016 ch.5/11, the edition Minnesota pins, mapped to 2019 ch.4/19): classifications are for sprinkler design only; light hazard, ordinary group 1 (8 ft stockpiles), ordinary group 2 (12 ft / 8 ft), extra hazard group 1 (dust, lint) and group 2 (liquids, shielding); the annex example lists (churches, hospitals, distilleries, mercantile, post offices, repair garages, car stackers). Density/area curves (any single point, 1,500/2,500 sq ft minimums, spray only, no QR in extra hazard), QR area reduction, +30% dry/double interlock and sloped ceilings, high-temp and 2019 K-11.2 reductions, 3,000 sq ft concealed-space rule, room design method (8 in. lintel), special design areas, hose stream and duration tables, pipe schedule, residential sprinklers in NFPA 13, 15 ft adjacent hazard rule, 400 sq ft rule. Minnesota: 903.3.1.4 undetermined use = OH2 over 3,000 sq ft, 903.3.1.5 chemistry labs and wrestling/gymnastics rooms, 903.3.1.6.1 fire chief can modify hose streams. App news: the MN Journeyman Exam Prep Android app has enough testers, and its 14-day countdown to going public on Google Play has started. Expect it on the Play Store in a couple of weeks, once Google finishes its review.
Embed this episode
No transcript yet.